1.0 AIM
To lay down a standard operating procedure for Decontamination of D.M. Water plant.
2.0 SCOPE
Maintenance Department
3.0 AREA OF OPERATION
Service floor.
4.0 RESPONSIBILITY
Operator/Maintenance Supervisor concerned.
5.0 ACCOUNTABILITY
Maintenance Incharge.
6.0 PROCEDURE
NOTE: Decontamination of D.M. Water plant is done as per recommendation of Q. C. department or once in a month; after regeneration of D.M. Water Plant.
6.1 Decontamination of Mixed Bed Unit
a) Mix 40 ml of formaldehyde solution with 200 ltr of D.M Water.
b) Inject this solution into mixed bed unit (MBU) by dipping tube attached to ejector E-2 into the formaldehyde solution and by opening valve 18, 20 & 22.
c) After completion of formalin injection close the valve 18, 20 & 22.
6.2 Decontamination of anionic exchanger
a) Mix 40 ml of formaldehyde solution with 200 ltr. D. M. Water.
b) Deep the tube attached to ejector into formaldehyde solution.
c) Open valve 4, 5, 6, 7 and adjsut valve 4 to maintain the flow.
d) After completion of injection close the valce 4, 5, 6 & 7
6.3 Decontamination of Cationic exchanger
a) Mix 40 ml of formaldehyde solution with 200 ltr. D.M. Water.
b) Deep the tube attached to ejector into formaldehyde solution.
c) Open valve 1, 2 & 3 and adjust the valve 2 to maintain the flow.
d) After completion of injection close the valce 1, 2, & 3.
6.4 Rinsing of columns
a) Next day start the D.M. Water plant (Ref. SOP-ME- ) and drain the water.
b) Give the sample of D. M. Water to Q.C.
c) After getting OK from Q. C. collect the D. M. Water into D. M. Water collection tank.
7.0 REVIEW DATE
After 2 years or when procedure is changed.